Single-Phase Transformers
Product Features:
- A wide spread Customer Support Network to provide Installation, Commissioning or maintenance support.
- Highly skilled manpower.
- Latest manufacturing and testing facility.
- Effective Quality assurance Plan for incoming material and for in-process.
- Customized terminal arrangement ranging from bus ducts, cable boxes and bare bushings.
Technical Specifications
Voltage: 12.7/0.23kV*Vector group: Li0 *Tapping range: ±2x2.5% | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | Impedance (%) | Dimension (mm) | Weight (kg) | ||||
B | C | D | Active | Oil | Total | |||||
1 | 15 | 52 | 213 | 2÷2.4 | 600 | 1050 | 300 | 92 | 50 | 168 |
2 | 25 | 67 | 333 | 700 | 1080 | 300 | 136 | 50 | 209 | |
3 | 37.5 | 92 | 420 | 750 | 1080 | 300 | 173 | 74 | 272 | |
4 | 50 | 108 | 570 | 800 | 1100 | 300 | 230 | 80 | 350 | |
5 | 75 | 148 | 933 | 850 | 1100 | 600 | 245 | 85 | 380 | |
6 | 100 | 192 | 1305 | 850 | 1280 | 600 | 285 | 115 | 460 |
Voltage: 22/0.23kV*Vector group: Li0 *Tapping range: ±2x2.5% | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | Impedance (%) | Dimension (mm) | Weight (kg) | ||||
B | C | D | Active | Oil | Total | |||||
1 | 15 | 52 | 213 | 2÷2.4 | 650 | 1050 | 300 | 120 | 70 | 220 |
2 | 25 | 67 | 333 | 680 | 1100 | 300 | 145 | 75 | 250 | |
3 | 37.5 | 92 | 420 | 680 | 1120 | 300 | 180 | 78 | 300 | |
4 | 50 | 108 | 570 | 680 | 1190 | 300 | 220 | 81 | 360 | |
5 | 75 | 148 | 933 | 720 | 1190 | 600 | 250 | 86 | 390 | |
6 | 100 | 192 | 1305 | 745 | 1200 | 600 | 280 | 94 | 470 |
Voltage: 35/0.23kV*Vector group: Li0 *Tapping range: ±2x2.5% | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | Impedance (%) | Dimension (mm) | Weight (kg) | ||||
B | C | D | Active | Oil | Total | |||||
1 | 15 | 52 | 213 | 2÷2.4 | 650 | 1050 | 300 | 120 | 70 | 220 |
2 | 25 | 67 | 333 | 680 | 1100 | 300 | 145 | 75 | 250 | |
3 | 37.5 | 92 | 420 | 680 | 1120 | 300 | 180 | 78 | 300 | |
4 | 50 | 108 | 570 | 680 | 1190 | 300 | 220 | 81 | 360 | |
5 | 75 | 148 | 933 | 720 | 1190 | 600 | 250 | 86 | 390 | |
6 | 100 | 192 | 1305 | 745 | 1200 | 600 | 280 | 94 | 470 |
Single-Phase Transformers Amorphous
Product Features:
- A wide spread Customer Support Network to provide Installation, Commissioning or maintenance support.
- Highly skilled manpower.
- Latest manufacturing and testing facility.
- Effective Quality assurance Plan for incoming material and for in-process.
- Customized terminal arrangement ranging from bus ducts, cable boxes and bare bushings.
Technical Specifications
Voltage: 35/0.23kV*Vector group: Li0 *Tapping range: ±2x2.5% | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | Impedance (%) | Dimension (mm) | Weight (kg) | ||||
B | C | D | Active | Oil | Total | |||||
1 | 15 | 14 | 213 | 2÷2.4 | 700 | 1050 | 300 | 122 | 60 | 210 |
2 | 25 | 19 | 333 | 700 | 1130 | 300 | 160 | 60 | 245 | |
3 | 37.5 | 26 | 420 | 760 | 1130 | 300 | 215 | 65 | 320 | |
4 | 50 | 31 | 570 | 250 | 1200 | 300 | 250 | 75 | 365 | |
5 | 75 | 42 | 933 | 950 | 1200 | 600 | 300 | 150 | 505 | |
6 | 100 | 54 | 1305 | 950 | 1300 | 600 | 345 | 150 | 575 |
Product Features
Single-Phase Transformers
- A widespread Customer Support Network to provide Installation, Commissioning or maintenance support.
- Highly skilled manpower.
- Latest manufacturing and testing facility.
- Effective Quality assurance Plan for incoming material and for in-process.
- Customized terminal arrangement ranging from bus ducts, cable boxes and bare bushings.
Conservator Type
Product Features:
- Low Loss and Low Noise
- Safe and Reliable Operation
- Powerful Name Plate Operating Capacity and Excellent Thermal Performance
- Convenient to Install and Maintain
- Elaborate Operation
- The bell type tank and the corrugated shell increases the strength of tank with beautiful appearance.
- The core and tank are well fixed and well protected during transportation.
- Reasonable winding layout method, supported by the interior and exterior strips. High-tension cardboard cylinders between coils increase the short-circuit withstand capacity.
- Advanced workmanship is used, such as crimp welding technology phase-assembly technology for winding, and cardboard process, etc.
- To meet the client's needs, we can provide products of other voltage ratios, Vector Groups, and rated capacities, as listed in the table.
Technical Specifications
Voltage: 6.3/0.4kV*Vector group: Dyn11 *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | Active | Oil | Total | ||||||
1 | 50 | 120 | 715 | 2 | 4 | 1260 | 810 | 1250 | 520 | 310 | 180 | 640 |
2 | 75 | 165 | 985 | 2 | 4 | 1260 | 820 | 1300 | 520 | 385 | 200 | 720 |
3 | 100 | 205 | 1250 | 2 | 4 | 1260 | 860 | 1330 | 520 | 425 | 210 | 750 |
4 | 160 | 280 | 1940 | 2 | 4 | 1350 | 880 | 1340 | 520 | 510 | 240 | 925 |
5 | 180 | 295 | 2090 | 2 | 4 | 1350 | 890 | 1370 | 520 | 575 | 250 | 1000 |
6 | 250 | 340 | 2600 | 2 | 4 | 1390 | 900 | 1420 | 520 | 690 | 230 | 1100 |
7 | 320 | 385 | 3170 | 2 | 4 | 1390 | 910 | 1470 | 660 | 790 | 250 | 1250 |
8 | 400 | 433 | 3820 | 2 | 4 | 1430 | 980 | 1470 | 660 | 940 | 275 | 1450 |
9 | 560(500) | 580(525) | 4810)4439) | 2 | 4 | 1500 | 1020 | 1590 | 660 | 1215 | 335 | 1790 |
10 | 630 | 780 | 5570 | 2 | 4 | 1660 | 1010 | 1570 | 660 | 1250 | 370 | 1900 |
11 | 750(800) | 845(872) | 6540(5942) | 2 | 5 | 1740 | 1080 | 1570 | 660 | 1400 | 4400 | 2100 |
12 | 1000 | 980 | 8550 | 1.5 | 5 | 1840 | 1120 | 1760 | 820 | 1660 | 460 | 2650 |
13 | 1250 | 1115 | 10690 | 1.5 | 5 | 1870 | 1180 | 1770 | 820 | 1950 | 490 | 3050 |
14 | 1600 | 1305 | 13680 | 1.5 | 6 | 1990 | 1290 | 1860 | 820 | 2300 | 660 | 3750 |
15 | 2000 | 1500 | 17100 | 1 | 6 | 1990 | 1290 | 1960 | 820 | 2625 | 740 | 4300 |
16 | 2500 | 1850 | 21000 | 1 | 6 | 2020 | 1360 | 2010 | 820 | 2900 | 800 | 4700 |
17 | 3200 | 2340 | 24460 | 1 | 7 | 2290 | 1530 | 2070 | 1070 | 4060 | 1075 | 6350 |
18 | Above 3200 | Manufacturing according to customers requirements |
Voltage: 6.3(10)-22/0.4kV*Vector group: Y(D)yn11(11) *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | Active | Oil | Total | ||||||
1 | 50 | 120 | 715 | 2 | 4 | 1290 | 810 | 1340 | 520 | 320 | 205 | 670 |
2 | 75 | 165 | 985 | 2 | 4 | 1300 | 830 | 1380 | 520 | 400 | 225 | 770 |
3 | 100 | 205 | 1250 | 2 | 4 | 1300 | 870 | 1410 | 520 | 425 | 225 | 800 |
4 | 160 | 280 | 1940 | 2 | 4 | 1400 | 890 | 1420 | 520 | 530 | 280 | 1000 |
5 | 180 | 295 | 2090 | 2 | 4 | 1400 | 900 | 1450 | 520 | 595 | 285 | 1075 |
6 | 250 | 340 | 2600 | 2 | 4 | 1430 | 930 | 1500 | 520 | 710 | 295 | 1215 |
7 | 320 | 385 | 3170 | 2 | 4 | 1380 | 930 | 1550 | 660 | 825 | 305 | 1340 |
8 | 400 | 433 | 3820 | 2 | 4 | 1480 | 940 | 1670 | 660 | 960 | 320 | 1650 |
9 | 560(500) | 580(525) | 4810)4439) | 2 | 4 | 1620 | 1020 | 1790 | 660 | 1085 | 400 | 2035 |
10 | 630 | 780 | 5570 | 2 | 4 | 1660 | 1050 | 1710 | 660 | 1350 | 400 | 2050 |
11 | 750(800) | 845(872) | 6540(5942) | 2 | 5 | 1810 | 1050 | 1710 | 660 | 1510 | 450 | 2330 |
12 | 1000 | 980 | 8550 | 1.5 | 5 | 1900 | 1140 | 1880 | 820 | 1780 | 510 | 2850 |
13 | 1250 | 1115 | 10690 | 1.5 | 5 | 1950 | 1140 | 1930 | 820 | 2030 | 550 | 3200 |
14 | 1600 | 1305 | 13680 | 1.5 | 6 | 2050 | 1250 | 1970 | 820 | 2440 | 660 | 3870 |
15 | 2000 | 1500 | 17100 | 1 | 6 | 2100 | 1290 | 2020 | 820 | 2800 | 735 | 4380 |
16 | 2500 | 1850 | 21000 | 1 | 6 | 2170 | 1400 | 2080 | 820 | 3280 | 850 | 5170 |
17 | 3200 | 2340 | 24460 | 1 | 7 | 2370 | 1480 | 2130 | 1070 | 4275 | 1100 | 6575 |
18 | Above 3200 | Manufacturing according to customers requirements |
Voltage: 22/0.4kV*Vector group: Dyn11 *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | Active | Oil | Total | ||||||
1 | 50 | 120 | 715 | 2 | 4 | 1270 | 810 | 1250 | 520 | 310 | 180 | 640 |
2 | 75 | 165 | 985 | 2 | 4 | 1270 | 820 | 1300 | 520 | 385 | 200 | 720 |
3 | 100 | 205 | 1250 | 2 | 4 | 1270 | 860 | 1330 | 520 | 425 | 210 | 750 |
4 | 160 | 280 | 1940 | 2 | 4 | 1360 | 880 | 1340 | 520 | 510 | 240 | 925 |
5 | 180 | 295 | 2090 | 2 | 4 | 1360 | 890 | 1370 | 520 | 575 | 250 | 1000 |
6 | 250 | 340 | 2600 | 2 | 4 | 1390 | 900 | 1420 | 520 | 690 | 230 | 1100 |
7 | 320 | 385 | 3170 | 2 | 4 | 1340 | 910 | 1470 | 660 | 790 | 250 | 1250 |
8 | 400 | 433 | 3820 | 2 | 4 | 1380 | 980 | 1470 | 660 | 940 | 275 | 1450 |
9 | 560(500) | 580(525) | 4810)4439) | 2 | 4 | 1500 | 1020 | 1660 | 660 | 1215 | 335 | 1790 |
10 | 630 | 780 | 5570 | 2 | 4 | 1660 | 1010 | 1640 | 660 | 1250 | 370 | 1900 |
11 | 750(800) | 845(872) | 6540(5942) | 2 | 5 | 1740 | 1080 | 1640 | 660 | 1400 | 400 | 2100 |
12 | 1000 | 980 | 8550 | 1.5 | 5 | 1840 | 1120 | 1760 | 820 | 1660 | 460 | 2650 |
13 | 1250 | 1115 | 10690 | 1.5 | 5 | 1870 | 1180 | 1770 | 820 | 1950 | 490 | 3050 |
14 | 1600 | 1305 | 13680 | 1.5 | 6 | 1990 | 1290 | 1860 | 820 | 2300 | 660 | 3750 |
15 | 2000 | 1500 | 17100 | 1 | 6 | 1990 | 1290 | 1960 | 820 | 2625 | 740 | 4300 |
16 | 2500 | 1850 | 21000 | 1 | 6 | 2020 | 1360 | 2010 | 820 | 2900 | 800 | 4700 |
17 | 3200 | 2340 | 24460 | 1 | 7 | 2290 | 1530 | 2070 | 1070 | 4060 | 1075 | 6350 |
18 | Above 3200 | Manufacturing according to customers requirements |
Voltage: 22/0.4kV*Vector group: Dyn11 *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | Active | Oil | Total | ||||||
1 | 50 | 120 | 715 | 2 | 4 | 1450 | 790 | 1520 | 520 | 370 | 270 | 800 |
2 | 75 | 165 | 985 | 2 | 4 | 1450 | 790 | 1560 | 520 | 425 | 275 | 865 |
3 | 100 | 205 | 1250 | 2 | 4 | 1470 | 850 | 1600 | 520 | 515 | 300 | 990 |
4 | 160 | 280 | 1940 | 2 | 4 | 1550 | 890 | 1600 | 520 | 675 | 350 | 1250 |
5 | 180 | 295 | 2090 | 2 | 4 | 1550 | 890 | 1640 | 520 | 745 | 355 | 1320 |
6 | 250 | 340 | 2600 | 2 | 4 | 1470 | 890 | 1620 | 520 | 785 | 320 | 1320 |
7 | 320 | 385 | 3170 | 2 | 4 | 1520 | 920 | 1650 | 660 | 980 | 345 | 1555 |
8 | 400 | 433 | 3820 | 2 | 4 | 1500 | 950 | 1750 | 660 | 1100 | 380 | 1750 |
9 | 560(500) | 580(525) | 4810)4439) | 2 | 4 | 1650 | 1000 | 1800 | 660 | 1380 | 470 | 2130 |
10 | 630 | 780 | 5570 | 2 | 4 | 1830 | 730 | 1720 | 660 | 1370 | 450 | 2135 |
11 | 750(800) | 845(872) | 6540(5942) | 2 | 5 | 1820 | 1050 | 1720 | 660 | 1155 | 520 | 2450 |
12 | 1000 | 980 | 8550 | 1.5 | 5 | 1850 | 1100 | 1940 | 820 | 1815 | 570 | 2950 |
13 | 1250 | 1115 | 10690 | 1.5 | 5 | 1870 | 1140 | 1990 | 820 | 2065 | 610 | 3300 |
14 | 1600 | 1305 | 13680 | 1.5 | 6 | 1990 | 1250 | 2030 | 820 | 2485 | 730 | 4000 |
15 | 2000 | 1500 | 17100 | 1 | 6 | 2040 | 1300 | 2020 | 820 | 2875 | 775 | 4515 |
16 | 2500 | 1850 | 21000 | 1 | 6 | 2120 | 1410 | 2130 | 820 | 3335 | 900 | 5265 |
17 | 3200 | 2340 | 24460 | 1 | 7 | 2290 | 1490 | 2190 | 1070 | 4385 | 1160 | 6745 |
18 | Above 3200 | Manufacturing according to customers requirements |
Voltage: 35/0.4kV*Vector group: Yyn11 *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | Active | Oil | Total | ||||||
1 | 50 | 120 | 715 | 2 | 4 | 1390 | 800 | 1480 | 520 | 360 | 220 | 725 |
2 | 75 | 165 | 985 | 2 | 4 | 1400 | 810 | 1500 | 520 | 415 | 235 | 800 |
3 | 100 | 205 | 1250 | 2 | 4 | 1440 | 870 | 1500 | 520 | 515 | 240 | 875 |
4 | 160 | 280 | 1940 | 2 | 4 | 1510 | 910 | 1540 | 520 | 475 | 260 | 1130 |
5 | 180 | 295 | 2090 | 2 | 4 | 1510 | 920 | 1680 | 520 | 655 | 270 | 1200 |
6 | 250 | 340 | 2600 | 2 | 4 | 1510 | 920 | 1550 | 520 | 720 | 280 | 1250 |
7 | 320 | 385 | 3170 | 2 | 4 | 1490 | 950 | 1570 | 660 | 770 | 300 | 1480 |
8 | 400 | 433 | 3820 | 2 | 4 | 1480 | 940 | 1670 | 660 | 960 | 320 | 1650 |
9 | 560(500) | 580(525) | 4810)4439) | 2 | 4 | 1620 | 1020 | 1790 | 660 | 1085 | 400 | 2035 |
10 | 630 | 780 | 5570 | 2 | 4 | 1660 | 1050 | 1710 | 660 | 1350 | 400 | 2050 |
11 | 750(800) | 845(872) | 6540(5942) | 2 | 5 | 1810 | 1050 | 1710 | 660 | 1510 | 450 | 2330 |
12 | 1000 | 980 | 8550 | 1.5 | 5 | 1900 | 1140 | 1880 | 820 | 1780 | 510 | 2850 |
13 | 1250 | 1115 | 10690 | 1.5 | 5 | 1950 | 1140 | 1930 | 820 | 2030 | 550 | 3200 |
14 | 1600 | 1305 | 13680 | 1.5 | 6 | 2050 | 1250 | 1970 | 820 | 2440 | 660 | 3870 |
15 | 2000 | 1500 | 17100 | 1 | 6 | 2100 | 1290 | 2020 | 820 | 2800 | 735 | 4380 |
16 | 2500 | 1850 | 21000 | 1 | 6 | 2170 | 1400 | 2080 | 820 | 3280 | 850 | 5170 |
17 | 3200 | 2340 | 24460 | 1 | 7 | 2370 | 1480 | 2130 | 1070 | 4275 | 1100 | 6575 |
18 | Above 3200 | Manufacturing according to customers requirements |
Hermetically Sealed Type
Product Features:
- Low Loss and Low Noise
- Safe and Reliable Operation
- Powerful Name Plate Operating Capacity and Excellent Thermal Performance
- Convenient to Install and Maintain
- Elaborate Operation
- The bell type tank and the corrugated shell increases the strength of tank with beautiful appearance.
- The core and tank are well fixed and well protected during transportation.
- Reasonable winding layout method, supported by the interior and exterior strips. High-tension cardboard cylinders between coils increase the short-circuit withstand capacity.
- Advanced workmanship is used, such as crimp welding technology phase-assembly technology for winding, and cardboard process, etc.
- To meet the client's needs, we can provide products of other voltage ratios, Vector Groups, and rated capacities, as listed in the table.
Technical Specifications
Voltage: 6.3/0.4kV*Vector group: Dyn11 *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | Active | Oil | Total | ||||||
1 | 50 | 120 | 715 | 2 | 4 | 970 | 890 | 1170 | 520 | 310 | 180 | 640 |
2 | 75 | 165 | 985 | 2 | 4 | 970 | 900 | 1210 | 520 | 385 | 200 | 720 |
3 | 100 | 205 | 1250 | 2 | 4 | 70 | 900 | 1240 | 520 | 425 | 210 | 750 |
4 | 160 | 280 | 1940 | 2 | 4 | 1060 | 920 | 1250 | 520 | 510 | 240 | 925 |
5 | 180 | 295 | 2090 | 2 | 4 | 1060 | 930 | 1280 | 520 | 575 | 250 | 1000 |
6 | 250 | 340 | 2600 | 2 | 4 | 1080 | 980 | 1130 | 520 | 690 | 230 | 1100 |
7 | 320 | 385 | 3170 | 2 | 4 | 1080 | 990 | 1180 | 660 | 790 | 250 | 1250 |
8 | 400 | 433 | 3820 | 2 | 4 | 1120 | 1020 | 1180 | 660 | 940 | 275 | 1450 |
9 | 560(500) | 580(525) | 4810)4439) | 2 | 4 | 1210 | 1060 | 1240 | 660 | 1215 | 335 | 1790 |
10 | 630 | 780 | 5570 | 2 | 4 | 1560 | 1080 | 1220 | 660 | 1250 | 370 | 1900 |
11 | 750(800) | 845(872) | 6540(5942) | 2 | 5 | 1620 | 1110 | 1220 | 660 | 1400 | 400 | 2100 |
12 | 1000 | 980 | 8550 | 1.5 | 5 | 1670 | 1120 | 1450 | 820 | 1660 | 460 | 2650 |
13 | 1250 | 1115 | 10690 | 1.5 | 5 | 1720 | 1180 | 1460 | 820 | 1950 | 490 | 3050 |
14 | 1600 | 1305 | 13680 | 1.5 | 6 | 1860 | 1290 | 1550 | 820 | 2300 | 660 | 3750 |
15 | 2000 | 1500 | 17100 | 1 | 6 | 1860 | 1290 | 1650 | 820 | 2625 | 740 | 4300 |
16 | 2500 | 1850 | 21000 | 1 | 6 | 1920 | 1360 | 1690 | 820 | 2900 | 800 | 4700 |
17 | 3200 | 2340 | 24460 | 1 | 7 | 2210 | 1530 | 1750 | 1070 | 4060 | 1075 | 6350 |
18 | Above 3200 | Manufacturing according to customers requirements |
Voltage: 6.3/0.4kV*Vector group: Dyn11 *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | Active | Oil | Total | ||||||
1 | 50 | 120 | 715 | 2 | 4 | 980 | 850 | 1220 | 520 | 320 | 205 | 670 |
2 | 75 | 165 | 985 | 2 | 4 | 980 | 870 | 1270 | 520 | 400 | 225 | 770 |
3 | 100 | 205 | 1250 | 2 | 4 | 990 | 870 | 1300 | 520 | 425 | 225 | 800 |
4 | 160 | 280 | 1940 | 2 | 4 | 1090 | 890 | 1310 | 520 | 530 | 280 | 1000 |
5 | 180 | 295 | 2090 | 2 | 4 | 1090 | 900 | 1340 | 520 | 595 | 285 | 1075 |
6 | 250 | 340 | 2600 | 2 | 4 | 1110 | 970 | 1310 | 520 | 710 | 295 | 1215 |
7 | 320 | 385 | 3170 | 2 | 4 | 1140 | 970 | 1380 | 660 | 825 | 305 | 1340 |
8 | 400 | 433 | 3820 | 2 | 4 | 1140 | 1000 | 1400 | 660 | 995 | 335 | 1550 |
9 | 560(500) | 580(525) | 4810)4439) | 2 | 4 | 1270 | 1040 | 1440 | 660 | 1270 | 420 | 1975 |
10 | 630 | 780 | 5570 | 2 | 4 | 1290 | 1060 | 1420 | 660 | 1285 | 435 | 2000 |
11 | 750(800) | 845(872) | 6540(5942) | 2 | 5 | 1670 | 1100 | 1500 | 660 | 1450 | 194 | 2325 |
12 | 1000 | 980 | 8550 | 1.5 | 5 | 1670 | 1100 | 1520 | 820 | 1700 | 550 | 2800 |
13 | 1250 | 1115 | 10690 | 1.5 | 5 | 1720 | 1160 | 1560 | 820 | 2000 | 590 | 3225 |
14 | 1600 | 1305 | 13680 | 1.5 | 6 | 1930 | 1320 | 1570 | 820 | 2420 | 755 | 4000 |
15 | 2000 | 1500 | 17100 | 1 | 6 | 1950 | 1360 | 1670 | 820 | 2700 | 785 | 4450 |
16 | 2500 | 1850 | 21000 | 1 | 6 | 2010 | 1400 | 1740 | 820 | 3050 | 885 | 4930 |
17 | 3200 | 2340 | 24460 | 1 | 7 | 2210 | 1510 | 1770 | 1070 | 4200 | 1145 | 6515 |
18 | Above 3200 | Manufacturing according to customers requirements |
Voltage: 22/0.4kV*Vector group: Dyn11 *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | Active | Oil | Total | ||||||
1 | 50 | 120 | 715 | 2 | 4 | 960 | 890 | 1170 | 520 | 310 | 180 | 640 |
2 | 75 | 165 | 985 | 2 | 4 | 960 | 900 | 1210 | 520 | 385 | 200 | 720 |
3 | 100 | 205 | 1250 | 2 | 4 | 960 | 900 | 1240 | 520 | 425 | 210 | 750 |
4 | 160 | 280 | 1940 | 2 | 4 | 1050 | 920 | 1250 | 520 | 510 | 240 | 925 |
5 | 180 | 295 | 2090 | 2 | 4 | 1050 | 930 | 1280 | 520 | 575 | 250 | 1000 |
6 | 250 | 340 | 2600 | 2 | 4 | 1070 | 980 | 1240 | 520 | 690 | 230 | 1100 |
7 | 320 | 385 | 3170 | 2 | 4 | 1070 | 990 | 131 | 660 | 790 | 250 | 1250 |
8 | 400 | 433 | 3820 | 2 | 4 | 1110 | 1020 | 1310 | 660 | 940 | 275 | 1450 |
9 | 560(500) | 580(525) | 4810)4439) | 2 | 4 | 1200 | 1060 | 1370 | 660 | 1215 | 335 | 1790 |
10 | 630 | 780 | 5570 | 2 | 4 | 1550 | 1090 | 1350 | 660 | 1250 | 370 | 1900 |
11 | 750(800) | 845(872) | 6540(5942) | 2 | 5 | 1610 | 1120 | 660 | 1400 | 400 | 2100 | |
12 | 1000 | 980 | 8550 | 1.5 | 5 | 1660 | 1120 | 820 | 1660 | 460 | 2650 | |
13 | 1250 | 1115 | 10690 | 1.5 | 5 | 1710 | 1180 | 1560 | 820 | 1950 | 490 | 3050 |
14 | 1600 | 1305 | 13680 | 1.5 | 6 | 1850 | 1290 | 1570 | 820 | 2300 | 660 | 3750 |
15 | 2000 | 1500 | 17100 | 1 | 6 | 1850 | 1290 | 1670 | 820 | 2625 | 740 | 4300 |
16 | 2500 | 1850 | 21000 | 1 | 6 | 1910 | 1360 | 1740 | 820 | 2900 | 800 | 4700 |
17 | 3200 | 2340 | 24460 | 1 | 7 | 2200 | 1530 | 1770 | 1070 | 4060 | 1075 | 6350 |
18 | Above 3200 | Manufacturing according to customers requirements |
Voltage: 35/0.4kV*Vector group: Dyn11 *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | Active | Oil | Total | ||||||
1 | 50 | 120 | 715 | 2 | 4 | 950 | 900 | 1410 | 520 | 360 | 220 | 725 |
2 | 75 | 165 | 985 | 2 | 4 | 990 | 910 | 1450 | 520 | 415 | 235 | 800 |
3 | 100 | 205 | 1250 | 2 | 4 | 1010 | 920 | 1480 | 520 | 475 | 240 | 875 |
4 | 160 | 280 | 1940 | 2 | 4 | 1050 | 960 | 1490 | 520 | 655 | 260 | 1130 |
5 | 180 | 295 | 2090 | 2 | 4 | 1050 | 960 | 1530 | 520 | 720 | 270 | 1200 |
6 | 250 | 340 | 2600 | 2 | 4 | 1080 | 1000 | 1450 | 520 | 770 | 280 | 1250 |
7 | 320 | 385 | 3170 | 2 | 4 | 1120 | 1030 | 1470 | 660 | 960 | 300 | 1480 |
8 | 400 | 433 | 3820 | 2 | 4 | 1110 | 1050 | 1570 | 660 | 1085 | 320 | 1650 |
9 | 560(500) | 580(525) | 4810)4439) | 2 | 4 | 1220 | 1060 | 1610 | 660 | 1350 | 400 | 2035 |
10 | 630 | 780 | 5570 | 2 | 4 | 1250 | 1090 | 1530 | 660 | 1350 | 400 | 2050 |
11 | 750(800) | 845(872) | 6540(5942) | 2 | 5 | 1600 | 1130 | 1540 | 660 | 1510 | 450 | 2330 |
12 | 1000 | 980 | 8550 | 1.5 | 5 | 1620 | 1140 | 1660 | 820 | 1780 | 510 | 2850 |
13 | 1250 | 1115 | 10690 | 1.5 | 5 | 1670 | 1140 | 1710 | 820 | 2030 | 550 | 3200 |
14 | 1600 | 1305 | 13680 | 1.5 | 6 | 1810 | 1250 | 1750 | 820 | 2440 | 660 | 3870 |
15 | 2000 | 1500 | 17100 | 1 | 6 | 1860 | 1290 | 1740 | 820 | 2800 | 735 | 4380 |
16 | 2500 | 1850 | 21000 | 1 | 6 | 1960 | 1400 | 1840 | 820 | 3280 | 850 | 5170 |
17 | 3200 | 2340 | 24460 | 1 | 7 | 2160 | 1480 | 1900 | 1070 | 4275 | 1100 | 6575 |
18 | Above 3200 | Manufacturing according to customers requirements |
Voltage: 22/0.4kV*Vector group: Dyn11 *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | Active | Oil | Total | ||||||
1 | 100 | 60 | 1250 | 2 | 4 | 1350 | 950 | 1220 | 660 | 550 | 285 | 1045 |
2 | 160 | 76 | 1940 | 2 | 4 | 1350 | 1000 | 1230 | 660 | 680 | 310 | 1215 |
3 | 250 | 100 | 2600 | 2 | 4 | 1370 | 1050 | 1240 | 660 | 1000 | 310 | 1550 |
4 | 320 | 116 | 3170 | 2 | 4 | 1600 | 1050 | 1350 | 660 | 1170 | 445 | 1915 |
5 | 400 | 132 | 3820 | 2 | 4 | 1370 | 1070 | 1350 | 660 | 1280 | 380 | 1930 |
6 | 560 | 176 | 4810 | 2 | 4 | 1680 | 1120 | 1390 | 660 | 1790 | 545 | 2730 |
7 | 630 | 216 | 5570 | 2 | 4 | 1650 | 1120 | 1400 | 660 | 1765 | 530 | 2685 |
8 | 400 | 232 | 6540 | 2 | 4 | 1780 | 1130 | 1410 | 660 | 2000 | 600 | 3020 |
9 | 560(500) | 248 | 6920 | 2 | 4 | 1800 | 1150 | 1430 | 660 | 2100 | 630 | 3350 |
10 | 630 | 280 | 8550 | 2 | 4 | 2120 | 1200 | 1460 | 820 | 2380 | 755 | 3850 |
11 | 750(800) | 336 | 10690 | 2 | 5 | 2400 | 1260 | 1520 | 820 | 2845 | 880 | 4600 |
12 | 1000 | 376 | 12825 | 1.5 | 5 | 2500 | 1280 | 1550 | 820 | 3150 | 900 | 5000 |
13 | 1250 | 392 | 13680 | 1.5 | 5 | 2500 | 1300 | 1570 | 820 | 3350 | 990 | 5300 |
14 | 1600 | 464 | 17100 | 1.5 | 6 | 2650 | 1320 | 1650 | 820 | 4210 | 1180 | 6500 |
15 | 2000 | 554 | 21740 | 1 | 6 | 2650 | 1350 | 1670 | 1070 | 4970 | 1180 | 7370 |
18 | Above 3200 | Manufacturing according to customers requirements |
Product Features
Three-Phase Oil-Immersed
- Low Loss and Low Noise
- Safe and Reliable Operation
- Powerful Name Plate Operating Capacity and Excellent Thermal Performance
- Convenient to Install and Maintain
- Elaborate Operation
- The bell type tank and the corrugated shell increases the strength of tank with beautiful appearance.
- The core and tank are well fixed and well protected during transportation.
- Reasonable winding layout method, supported by the interior and exterior strips. High-tension cardboard cylinders between coils increase the short-circuit withstand capacity.
- Advanced workmanship is used, such as crimp welding technology phase-assembly technology for winding, and cardboard process, etc.
- To meet the client's needs, we can provide products of other voltage ratios, Vector Groups, and rated capacities, as listed in the table.
Three-Phase Cast Resin (Dry type)
Product Features:
- Low Loss and Low Noise
- Safe and Reliable Operation
- Powerful Name Plate Operating Capacity and Excellent Thermal Performance
- Convenient to Install and Maintain
- Elaborate Operation
- The bell type tank and the corrugated shell increases the strength of tank with beautiful appearance.
- The core and tank are well fixed and well protected during transportation.
- Reasonable winding layout method, supported by the interior and exterior strips. High-tension cardboard cylinders between coils increase the short-circuit withstand capacity.
- Advanced workmanship is used, such as crimp welding technology phase-assembly technology for winding, and cardboard process, etc.
- To meet the client's needs, we can provide products of other voltage ratios, Vector Groups, and rated capacities, as listed in the table.
Technical Specifications
Voltage: 22/0.4kV*Vector group: Dyn11 *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | |||||||||
1 | 250 | 850 | 3959 | 2 | 4 | 1150 | 990 | 1210 | 660 | 1100 | ||
2 | 320 | 1020 | 4620 | 2 | 4 | 1195 | 1000 | 1250 | 660 | 1230 | ||
3 | 400 | 1150 | 5405 | 2 | 4 | 1260 | 1020 | 1250 | 660 | 1300 | ||
4 | 560 | 1610 | 6900 | 2 | 4 | 1270 | 1060 | 1320 | 820 | 1800 | ||
5 | 630 | 1700 | 7130 | 2 | 4 | 1330 | 1060 | 1380 | 820 | 1800 | ||
6 | 750 | 2050 | 7498 | 2 | 5 | 1310 | 1110 | 1430 | 820 | 2000 | ||
7 | 1000 | 2400 | 8211 | 1.5 | 5 | 1370 | 1120 | 1500 | 820 | 2300 | ||
8 | 1250 | 2850 | 11914 | 1.5 | 5 | 1400 | 1120 | 1600 | 820 | 2700 | ||
9 | 1600 | 3300 | 13110 | 1.5 | 6 | 1480 | 1150 | 1750 | 820 | 3200 | ||
10 | 2000 | 4100 | 14111 | 1 | 6 | 1650 | 1300 | 1770 | 1070 | 3800 | ||
11 | 2500 | 5150 | 17411 | 1 | 6 | 1750 | 1300 | 1770 | 1070 | 5000 | ||
12 | 3200 | 6050 | 21505 | 1 | 7 | 1750 | 1350 | 1850 | 1070 | 5900 | ||
13 | Above 3200 |
Product Features
Three-Phase Cast Resin (Dry Type)
- This transformer has good heat dissipation, and its coil does not absorb moisture. It does not pollute the environment, and can be installed in the loading center.
- Low noise and low loss. It is energy-saving, economic and free from maintenance
- It has high mechanical strength, strong insulation and good short circuit withstand capacity.
- It has good fire protection, anti explosion and disaster-prevention performance.
- Low loss, small in size, light in weight, and easy to install.
- It has long life expectancy and strong overloading ability. It can operate continuously, and it could also operate at rated capacity without forced cooling.
- It has very high safety and fire prevention properties, without smoke generated.
- It has excellent thermal shock resistance.
- 100% waterproof sealing.
- After service life, the insulation materials and copper wire can be easily detached and recycled with no pollution to the environment.
Conservator Type
Product Features:
- Low Loss and Low Noise
- Safe and Reliable Operation
- Powerful Name Plate Operating Capacity and Excellent Thermal Performance
- Convenient to Install and Maintain
- Elaborate Operation
- The bell type tank and the corrugated shell increases the strength of tank with beautiful appearance.
- The core and tank are well fixed and well protected during transportation.
- Reasonable winding layout method, supported by the interior and exterior strips. High-tension cardboard cylinders between coils increase the short-circuit withstand capacity.
- Advanced workmanship is used, such as crimp welding technology phase-assembly technology for winding, and cardboard process, etc.
- To meet the client's needs, we can provide products of other voltage ratios, Vector Groups, and rated capacities, as listed in the table.
Technical Specifications
Voltage: 22/0.4kV*Vector group: Dyn11 *Tapping range: ±2x2.5% | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Number | Capacity (kVA) | No-load Losses (W) | Load losses (w) | No-load Current (%) (W) | Impedance (%) | Dimension (mm) | Weight (kg) | |||||
A | B | C | D | Active | Oil | Total | ||||||
1 | 100 | 75 | 1258 | 2 | 4÷6 | 1200 | 800 | 1280 | 520 | 520 | 225 | 915 |
2 | 160 | 95 | 1940 | 2 | 4÷6 | 1340 | 800 | 1250 | 520 | 680 | 260 | 1135 |
3 | 180 | 115 | 2185 | 2 | 4÷6 | 1340 | 800 | 1250 | 520 | 700 | 255 | 1160 |
4 | 250 | 125 | 2600 | 2 | 4÷6 | 1350 | 1020 | 1350 | 660 | 900 | 320 | 1495 |
5 | 320 | 145 | 3330 | 2 | 4÷6 | 1440 | 1020 | 1350 | 660 | 1030 | 340 | 1670 |
6 | 400 | 165 | 3818 | 2 | 4÷6 | 1450 | 1050 | 1460 | 660 | 1250 | 380 | 1940 |
7 | 500(560) | 220 | 4810 | 2 | 4÷6 | 1700 | 1080 | 1500 | 660 | 1600 | 470 | 2475 |
8 | 630 | 270 | 5570 | 2 | 4÷6 | 1520 | 1150 | 1450 | 660 | 1660 | 480 | 2500 |
9 | 750 | 290 | 6725 | 2 | 4÷6 | 1700 | 1200 | 1520 | 820 | 1875 | 515 | 2815 |
10 | 800 | 310 | 6920 | 2 | 4÷6 | 2200 | 1220 | 1600 | 820 | 2180 | 630 | 3475 |
11 | 1000 | 350 | 8550 | 2 | 4÷6 | 2300 | 1350 | 1620 | 820 | 2800 | 860 | 4430 |
12 | 1250 | 420 | 10690 | 1.5 | 4÷6 | 2200 | 1280 | 1750 | 820 | 3140 | 1150 | 5120 |
13 | ...... | Manufacturing according to customers requirements |
Product Features
Three-Phase Amorphous
- Low Loss and Low Noise
- Safe and Reliable Operation
- Powerful Name Plate Operating Capacity and Excellent Thermal Performance
- Convenient to Install and Maintain
- Elaborate Operation
- The bell type tank and the corrugated shell increases the strength of tank with beautiful appearance.
- The core and tank are well fixed and well protected during transportation.
- Reasonable winding layout method, supported by the interior and exterior strips. High-tension cardboard cylinders between coils increase the short-circuit withstand capacity.
- Advanced workmanship is used, such as crimp welding technology phase-assembly technology for winding, and cardboard process, etc.
- To meet the client's needs, we can provide products of other voltage ratios, Vector Groups, and rated capacities, as listed in the table.
Power Transformer with capacity of 25/40/63 MVA, Voltage up to 115KV
Product Features:
- Low Loss and Low Noise
- Safe and Reliable Operation
- Powerful Name Plate Operating Capacity and Excellent Thermal Performance
- Convenient to Install and Maintain
- Elaborate Operation
- The bell type tank and the corrugated shell increases the strength of tank with beautiful appearance.
- The core and tank are well fixed and well protected during transportation.
- Reasonable winding layout method, supported by the interior and exterior strips. High-tension cardboard cylinders between coils increase the short-circuit withstand capacity.
- Advanced workmanship is used, such as crimp welding technology phase-assembly technology for winding, and cardboard process, etc.
- To meet the client's needs, we can provide products of other voltage ratios, Vector Groups, and rated capacities, as listed in the table.
Technical Specifications
110 kV transformer, 2 Windings and Balance Coil Regulated Under Load | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Capacity (kVA) | Voltage | PO (kW) | Ok (kW) | UK (%) | Wiring Unit | Preliminary Weight Tons | Preliminary Weight Tons | |||||||
High Voltage Coil (HV) | Adjustment Range | Medium Voltage Coil (MV) | Equalizer Coil (LV) | Inside | Oil | Total | Length | Width | Height | |||||
25000 | 115 | ±9x1.78% | 23(24) | 11 | 15 | 105 | 11 | Y Nyn0 + d11 | 29 | 18 | 57 | 6500 | 5200 | 5600 |
40000 | 115 | ±9x1.78% | 23(24) | 11 | 18 | 160 | 11 | Y Nyn0 + d12 | 45 | 23 | 80 | 6700 | 5300 | 5800 |
63000 | 115 | ±9x1.78% | 23(24) | 11 | 28 | 190 | 11 | Y Nyn0 + d13 | 62 | 33 | 114 | 7300 | 5500 | 5900 |
Product Features
Power Transformers
- Low loss: No-load losses is about 40% lower than that required in current national standard
- Low noise level: <60dB, about 20dB lower than that required in the national standard
- Low partial discharge: the full range process of 220kV product is dust-free operation; metal parts and insulation parts inside the transformer are all rounded.
- High short-circuit capacity: the independently designed transformer of the Company has passed the short-circuit test.
- Beautiful appearance: oil tank bending corrugated structure, shot blasting de-dusting, powder EFI paint, wide fin radiator, never fade in color.
- No leakage: all seal with limit position and upper & lower tank edges are sealed along two channels; sealing gasket is imported. We solemnly commit no leakage of oil.